7 Mistakes You’re Making with Access Control on Fire Doors (and How to Fix Them)

Nov 19, 2026 | CCTV

It’s one of the classic "tug-of-war" moments in building management. On one side, you have security: you want to keep unauthorised people out. On the other side, you have fire safety: you need to let everyone out instantly if the alarm goes off.

When you start putting electronic locks on fire doors, these two worlds collide. If you get it right, your building is secure, compliant, and safe. If you get it wrong, you aren’t just failing a safety audit: you’re potentially putting lives at risk.

At JKE Fire & Security, we see these mistakes all the time. Usually, they aren't made out of negligence, but because the regulations (like BS 7273-4) can be a bit of a headache to navigate.

Here are the seven most common mistakes we see with access control on fire doors, and: more importantly: how to fix them.


1. Using "Fail-Secure" Locks on Escape Routes

This is the single most dangerous mistake a business can make.

In the world of access control, there are two types of locks:

  • Fail-Safe: The lock needs power to stay locked. If the power goes out, the door unlocks automatically.
  • Fail-Secure: The lock needs power to unlock. If the power goes out, the door stays locked.

The Mistake: Using fail-secure locks (like certain electric strikes or bolts) on a door that is a designated fire exit. If a fire cuts the power to the building, that door will stay locked, trapping people inside.

The Fix: Any door on an escape route must be fail-safe. Under UK law and BS 7273-4, if the power fails or the fire alarm is triggered, the door must default to an unlocked state so people can get out without needing a key, a code, or a fob.

A JKE engineer holding a fail-safe electromagnetic lock


2. No Direct Link to the Fire Alarm System

We’ve walked into many buildings where the access control system and the fire alarm system are like two neighbours who haven't spoken in years. They operate completely independently.

The Mistake: Relying on the access control system to work "as normal" during a fire. If the fire alarm goes off, the doors don't automatically unlock because there’s no interface between the two systems. You’re then relying on people to remember their fobs or find a break-glass unit in a smoke-filled corridor.

The Fix: Your access control system must be interfaced with your fire alarm. When the alarm is triggered, it should send a signal to the access control panel to drop the power to all fail-safe locks on the escape routes immediately.


3. Picking the Wrong BS 7273-4 Category

BS 7273-4 is the British Standard that governs how fire alarms and electronic locks should talk to each other. It breaks things down into three categories: A, B, and C.

The Mistake: Defaulting to Category C (the least stringent) because it’s cheaper or easier to install, even when the building’s risk level requires Category A.

  • Category A (Critical): The most robust. Even if the cable between the fire alarm and the door is cut, or if there’s a system fault, the door must fail-safe and unlock.
  • Category B & C: Lower levels of monitoring and fail-safety.

The Fix: If you are managing a high-risk building, such as a healthcare environment, a school, or a multi-occupancy residential block, you likely need Category A or B. Always check your Fire Risk Assessment (FRA) to see what level of protection is required for your specific site.


4. Forgetting the Green Break-Glass Unit

Even with a fire alarm interface and fail-safe locks, things can go wrong. Relays can stick, or wires can melt. This is why you need a manual override.

The Mistake: Thinking a "Request to Exit" (REX) button or a PIR sensor is enough. These are electronic devices that can fail.

The Fix: Every electronically locked fire door must have a Green Emergency Break-Glass unit (often called a "Green Box") on the exit side. This is a physical switch that cuts the power to the lock directly, bypassing all the software and control boards. It is the "last resort" that ensures anyone can get out in an emergency.

Emergency door release green break-glass unit and no-touch exit button


5. Compromising the Integrity of the Fire Door

A fire door is a carefully engineered piece of life-safety equipment. It’s designed to hold back smoke and flames for a specific amount of time (usually 30 or 60 minutes).

The Mistake: Hiring a security installer who doesn't understand fire doors. They might drill large holes for cables, cut out big chunks of the frame for an electric strike, or remove intumescent seals. This effectively ruins the door's fire rating. In a fire, the door might stay closed, but the smoke will pour through the gaps you've created.

The Fix: Use hardware that is specifically fire-rated and tested for the door it's being installed on. Cables should be hidden in fire-rated concealed loops, and any holes drilled should be treated with intumescent paste. At JKE, we ensure that every piece of hardware we fit maintains the door's integrity.


6. Using "Acoustic" Door Releases for Locks

You’ve probably seen those little battery-powered wedges that "listen" for a fire alarm and then drop the door closed. These are great for holding open fire doors in a corridor (like Dorgard units), but they should never be used for security locks.

The Mistake: Trying to use an acoustic listener to trigger the unlocking of a security door.

The Fix: Acoustic devices are not reliable enough for unlocking escape routes. They can be fooled by loud music, or they might not hear the alarm if it’s on a different floor or if the sounder is muffled. For locks, you need a hardwired connection to the fire alarm system.


7. The "Set and Forget" Mentality

This is perhaps the most common mistake of all. You’ve had the system installed, it passed the initial inspection, and you never think about it again.

The Mistake: Not testing the fire release regularly. Over time, relays can fail, backup batteries can die, and doors can drop on their hinges, causing locks to jam. If you don't find these problems during a test, you’ll find them during an emergency.

The Fix: Under the Regulatory Reform (Fire Safety) Order 2005, you have a legal duty to maintain your fire safety systems. You should be testing your door releases weekly as part of your fire alarm test and having a professional service the system at least twice a year.

JKE engineer performing maintenance on an access control panel


How to Get It Right

Managing the balance between security and safety doesn't have to be a headache. It just requires a bit of planning and the right professional advice.

When we work with business owners and facilities managers, we take a "solution-led" approach. We don't just "shift boxes" and install fobs; we look at the whole picture:

  1. Risk Assessment: What does your building actually need?
  2. Compliance: Are we meeting BS 7273-4 and the Building Regs?
  3. Simplicity: Is the system easy for your staff to use every day?
  4. Support: Who do you call at 2:00 AM if a door won't lock? (Hint: It’s us).

If you’re worried that your current setup might be making one of these mistakes, don't wait for your next fire inspection to find out. Give us a shout, and we can perform a site survey to make sure your people stay safe and your property stays secure.

Protecting your people, property, and reputation is what we do. Let’s make sure your fire doors are doing their job properly.